Telecom / Network Power SolutionsFor Information call:
North America: +1 (954) 346-2442 x1071
Europe: +44 (0)1903 768200
View Cart
North America: +1 (954) 346-2442 x1071
Europe: +44 (0)1903 768200
View Cart
Vigilant Series - Smart PDUs
All products can be customized to meet specific requirements.
One Mounting Position High - HTTP, SNMP, Email Communications
PDF Datasheets
For Support call:
North America: 954-346-2442 x1071
Europe: +44(0) 1903 768 200
North America: 954-346-2442 x1071
Europe: +44(0) 1903 768 200
Models Available
| Models | Output Current | Frequency | Nominal Voltage | Outlets | Buy |
|---|---|---|---|---|---|
| PDUAC1US-E*** | 16A (12A)* | 50/60Hz | 230VAC |
8 x IEC60320 C13** |
|
| PDUAC1US-N*** | 15A (12A)* | 50/60Hz | 115VAC |
8 x NEMA 5-15/20R** |
NOTES: *UL Derating.
**Input via IEC60320-C20.
***115V models supplied with ~10ft (3m) IEC60320-C19 to NEMA 5-15P, Power Cord. 230V models supplied with ~10ft (3m) IEC60320-C19 to IEC60320-C20 Power Cord.
**Input via IEC60320-C20.
***115V models supplied with ~10ft (3m) IEC60320-C19 to NEMA 5-15P, Power Cord. 230V models supplied with ~10ft (3m) IEC60320-C19 to IEC60320-C20 Power Cord.
Features and Options
| True RMS Digital Current Meter |
| Remote Power Monitoring via WEB, SNMP & Bundled Software |
| HTTP, HTTPS, SNMP, DHCP & UDP |
| Protocols Supported |
| Individual Outlet Switching |
| User Programmable ON/OFF Sequencing |
| User Programmable Alarm Thresholds |
| Event Alerts via Email, SNMP Trap |
| Audible Alarm |
Specifications Overview
| One Mounting Position High |
| HTTP, SNMP, Email Communications |
Safety Standards
| UL60950-1 (LISTED) |
| CSA22.2, No. 60950-1 |
| EN60950-1 |
Warranty
| Two Years |
Input Specifications
| Input Voltage Range: | 40-60VDC |
| Inrush Current Limiting: | 10A Peak |
| Input EMI Filter: | Standard |
| Analog Voltage Adjust: | 0 to +5V |
| Input Immunity, Conducted | |
| - Fast Transients, Line-Line: | ±500V (EN61000-4-4) |
| - Surges, Line-Line: | ±500V (EN61000-4-5) |
| - Surges, Input Ground: | ±500V (EN61000-4-5) |
| Input Protection: | Internal Fuse, 30A |
Output Specifications
| Voltage Range | |
| - 115VAC Nominal: | 100-127VAC |
| - 230VAC Nominal: | 200-240VAC |
| Output Current | |
| - 115VAC Nominal: | 15A (12A UL Derated) |
| - 230VAC Nominal: | 16A (12A UL Derated) |
| Frequency: | 50/60HZ |
| Protection | |
| - 115VAC Nominal: | 15A Resettable Circuit Breaker |
| - 230VAC Nominal: | 16A Resettable Circuit Breaker |
Physical Specifications
| Case Material: | Black Powder Coated Steel |
| Dimensions, Inches (mm): | 1.7H x 17.0W x 3.5D (44 x 432 x 90) |
| Rack Mounting: | 19”, 1U High |
| Weight: | 6.6lbs (3Kg) |
Environmental Specifications
| Operating Temp. Range: | 0ºC to 40ºC |
| Storage Temp. Range: | -40ºC to +85ºC |
| Humidity: | 0% to 90%, Non-Condensing |